My direct (no heat exchanger) solar hot water system pump runs an hour or two longer than I think it should in the late afternoon. Later in the day it continues to run when there is very little sunshine and for one or two hours it seems to be pulling hotter water up to the collector than it is returning to the tank. It doesn’t seem to shut down as early as I think it should and so theoretically seems to be wasting hot water at the end of the day.
Hoping someone might be able to give me some suggestions as to why this happens. All components otherwise seem to work as they should. The pump starts up when it should in the morning and seems to produce lots of hot water thru the day when the sun is shining. I have double checked all components and both sensors resistance tests out as specified and the controller (Steca TR301U) starts and stops when the T1 and T2 temps displayed match the default settings specified in the manual. Water temperature returning from the collector to the tank as measured by feeling the pipe from the collector as it enters the top of the tank seems to roughly match the T1 temperature displayed on the controller at all times of the day so I think it’s giving me good measurements.
The bottom of the tank T2 temperature does warm up but very slowly over the course of the day. In the morning temps are mid 80’sF and will increase up to 5F over the day in the Hawaii winter . Much more in summer. The tank is a top connected older 80 gal solar tank with upper element (rarely needed even in Hawaii winter and hasn’t been powered on for this discussion). It seems the tank remains stratified most days with cooler water staying at the bottom. As mentioned we have lots of hot water for two people so the top of the tank is quite warm without the heating element needing to be powered. With higher usage by more people we will sometimes power it up. All dip tubes have been checked, recently replaced, and deliver cold water to near the bottom of the tank, pull water from near the bottom of the tank up to the pump and on to the collector. Water from the collector is delivered by the dip tube to the middle of the tank 6 inches below the single upper element. (Mid tank)
Depending on the day, most days roughly between 4 -5 pm, comparing the temperature (by hand) of the pipe between the top of the tank and the pump (heading up to the collector) and the temperature of the pipe returning from the collector to the tank, the water moving up to the collector is significantly warmer than the water returning to the tank. The temperature of the returning water seems to match the T1 reading quite well as mentioned so I believe this component is operating correctly. The temp of the water moving up to the pump and then up to the collector is much hotter than the T2 temp displayed.
As mentioned, I’m confident the dip tube delivering water to the pump is intact and pulling cooler water from near the bottom of the tank, so my only explanation of what’s happening is that as water from the lower part of the tank moves up through the dip tube it is being heated by the hotter water in the upper part of the tank. Enough that later in the day when the collector has cooled off the system is sending warm water up and it is being cooled by the collector. T1-T2 differential temps don’t drop enough to shut the system down as soon as it should as the T2 measurement remains low with only slight increase in temp as the day goes on.
Apologies for the long description. So my question is, is this normal behavior for a top connected tank system?
My three thoughts are:
1. This is normal behavior and this is the reason why side connect tanks are available and preferable. In a side connect setup water going to the pump and the connector is pulled directly from the lower part of the side of the tank and does not pass through the hotter water in the upper tank.
2. Perhaps the pump is not moving water up from the bottom of the tank thru the dip tube fast enough to keep it from heating excessively as it passes up thru the upper part of the tank? It does seem to move water fast enough to produce good hot water passing thru the tank on sunny days. Could it be partial blockage, trapped air, or an underpowered pump? (Pump is brand new, replaced as identical to the previous one. This behavior happened with both pumps and didn’t change with the new pump). (Grundfos UP 15-29, bottom of tank to top of collector is ~ 13 ft).
3. The tank is remaining too stratified and I’m not getting enough mixing in the bottom of the tank to bring T2 temps up as the day goes on to make T1-T2 differential low enough to stop the pump at the right time. Should my dip tube from the connector be longer and move heated water lower in the tank to mix things up a bit.
Thanks in advance for your thoughts. Conrad
Hoping someone might be able to give me some suggestions as to why this happens. All components otherwise seem to work as they should. The pump starts up when it should in the morning and seems to produce lots of hot water thru the day when the sun is shining. I have double checked all components and both sensors resistance tests out as specified and the controller (Steca TR301U) starts and stops when the T1 and T2 temps displayed match the default settings specified in the manual. Water temperature returning from the collector to the tank as measured by feeling the pipe from the collector as it enters the top of the tank seems to roughly match the T1 temperature displayed on the controller at all times of the day so I think it’s giving me good measurements.
The bottom of the tank T2 temperature does warm up but very slowly over the course of the day. In the morning temps are mid 80’sF and will increase up to 5F over the day in the Hawaii winter . Much more in summer. The tank is a top connected older 80 gal solar tank with upper element (rarely needed even in Hawaii winter and hasn’t been powered on for this discussion). It seems the tank remains stratified most days with cooler water staying at the bottom. As mentioned we have lots of hot water for two people so the top of the tank is quite warm without the heating element needing to be powered. With higher usage by more people we will sometimes power it up. All dip tubes have been checked, recently replaced, and deliver cold water to near the bottom of the tank, pull water from near the bottom of the tank up to the pump and on to the collector. Water from the collector is delivered by the dip tube to the middle of the tank 6 inches below the single upper element. (Mid tank)
Depending on the day, most days roughly between 4 -5 pm, comparing the temperature (by hand) of the pipe between the top of the tank and the pump (heading up to the collector) and the temperature of the pipe returning from the collector to the tank, the water moving up to the collector is significantly warmer than the water returning to the tank. The temperature of the returning water seems to match the T1 reading quite well as mentioned so I believe this component is operating correctly. The temp of the water moving up to the pump and then up to the collector is much hotter than the T2 temp displayed.
As mentioned, I’m confident the dip tube delivering water to the pump is intact and pulling cooler water from near the bottom of the tank, so my only explanation of what’s happening is that as water from the lower part of the tank moves up through the dip tube it is being heated by the hotter water in the upper part of the tank. Enough that later in the day when the collector has cooled off the system is sending warm water up and it is being cooled by the collector. T1-T2 differential temps don’t drop enough to shut the system down as soon as it should as the T2 measurement remains low with only slight increase in temp as the day goes on.
Apologies for the long description. So my question is, is this normal behavior for a top connected tank system?
My three thoughts are:
1. This is normal behavior and this is the reason why side connect tanks are available and preferable. In a side connect setup water going to the pump and the connector is pulled directly from the lower part of the side of the tank and does not pass through the hotter water in the upper tank.
2. Perhaps the pump is not moving water up from the bottom of the tank thru the dip tube fast enough to keep it from heating excessively as it passes up thru the upper part of the tank? It does seem to move water fast enough to produce good hot water passing thru the tank on sunny days. Could it be partial blockage, trapped air, or an underpowered pump? (Pump is brand new, replaced as identical to the previous one. This behavior happened with both pumps and didn’t change with the new pump). (Grundfos UP 15-29, bottom of tank to top of collector is ~ 13 ft).
3. The tank is remaining too stratified and I’m not getting enough mixing in the bottom of the tank to bring T2 temps up as the day goes on to make T1-T2 differential low enough to stop the pump at the right time. Should my dip tube from the connector be longer and move heated water lower in the tank to mix things up a bit.
Thanks in advance for your thoughts. Conrad
Comment