I am having trouble with the performance of my Sunpower system. This started after an FW update that was installed last year as part of a snow-damage repair.
Before the damage, my 14 panel on grid microinverter system installed in the high desert (where solar intensity is between 108% and 120% of standard conditions) would report 5.16kW power produced in full sun. This is perfectly aligned with the 366VA rating marked on the microinverters.
With one panel destroyed, the system reported 4.8kW in full sun.
With the broken panel replaced, but the FW updated, the sunpower monitoring system reports 4.38kW in full sun.
I made some independent measurements:
20.84A * 247 V => 5.147kVA
However, the SCE power meter with all breakers in the house tripped shows -4.3kW power consumption
The difference must be caused by a steep-ish power factor of 0.83
The inverters are also marked 1.45A max each and 14*1.45 = 20.3A, so measured current is a little higher than the max rated current.
So is this behavior expected and the FW update changed reporting VA as W to reporting W properly? Or did the update reduce the max current the microinverters to their rated specification?
Is anybody else having a similar issue?
Before the damage, my 14 panel on grid microinverter system installed in the high desert (where solar intensity is between 108% and 120% of standard conditions) would report 5.16kW power produced in full sun. This is perfectly aligned with the 366VA rating marked on the microinverters.
With one panel destroyed, the system reported 4.8kW in full sun.
With the broken panel replaced, but the FW updated, the sunpower monitoring system reports 4.38kW in full sun.
I made some independent measurements:
20.84A * 247 V => 5.147kVA
However, the SCE power meter with all breakers in the house tripped shows -4.3kW power consumption
The difference must be caused by a steep-ish power factor of 0.83
The inverters are also marked 1.45A max each and 14*1.45 = 20.3A, so measured current is a little higher than the max rated current.
So is this behavior expected and the FW update changed reporting VA as W to reporting W properly? Or did the update reduce the max current the microinverters to their rated specification?
Is anybody else having a similar issue?